Heat pumps are efficient but need special care in cold weather. Learn about defrost cycles, auxiliary heat, and winter maintenance to stay warm.
Understanding the Defrost Cycle
In heating mode, the heat pump outdoor coil is colder than the outside air. Moisture in the air condenses on the coil and freezes into frost. As frost accumulates, it reduces airflow and efficiency. The heat pump senses this (via temperature sensor or pressure differential) and initiates a defrost cycle. During defrost, the system temporarily reverses to cooling mode—the hot refrigerant from the compressor flows through the outdoor coil, melting the frost. The outdoor fan stops to accelerate heating, and steam rises from the unit. The indoor unit engages auxiliary heat (electric strip heaters) to prevent cold air from blowing into the house. Defrost lasts 5–15 minutes, then the system returns to heating mode. Frequent or prolonged defrost cycles indicate a problem.
Winter Maintenance Checklist
Maintain your heat pump for winter efficiency with these steps. Monthly: check and replace or clean the air filter (clogged filters reduce efficiency and can cause defrost problems). Clear snow and ice from around the outdoor unit (maintain 2 feet clearance on all sides). Remove leaves and debris from the outdoor unit cabinet. Check the condensate drain for ice blockage. Seasonal (fall): schedule a professional tune-up—they will check refrigerant charge, clean the coils, inspect the defrost control, and verify auxiliary heat operation. Winter-specific: watch for ice buildup on the outdoor unit between defrost cycles (excessive ice means a problem). Check the auxiliary heat operation by raising the thermostat 5°F above room temperature—you should feel warm air from vents within 5 minutes.
Managing Auxiliary (Emergency) Heat
Auxiliary heat (often called electric resistance heat or strip heat) activates when the heat pump cannot keep up with demand—typically when outdoor temperatures drop below the system's balance point. Auxiliary heat is less efficient (1:1 efficiency vs. the heat pump's 2:1 to 4:1) and more expensive to run. Signs that auxiliary heat is running: higher energy bills, the thermostat display shows AUX or EM HEAT, and warm air from vents when the outdoor unit appears to be in defrost. To minimize auxiliary heat use: set the thermostat to a consistent temperature (frequent setbacks force auxiliary heat use during recovery), keep the filter clean, and ensure the outdoor unit is clear of debris and snow. If auxiliary heat runs excessively, the heat pump may need service or the balance point may need adjustment.
Cold-Climate Heat Pumps
Cold-climate heat pumps (sometimes called hyper-heat or low-ambient models) use advanced compressor technology—typically inverter-driven scroll compressors with vapor injection. They deliver full heating capacity at temperatures as low as -10°F to -15°F. Key features: variable-speed compressors adjust output to match demand, enhanced coil designs extract heat from very cold air, and sophisticated defrost controls minimize defrost frequency. These units carry HSPF (Heating Seasonal Performance Factor) ratings of 10+ and COP (Coefficient of Performance) of 2.0+ at 5°F. They cost 15–25% more than standard heat pumps but eliminate or reduce the need for auxiliary heat in cold climates. If you live in an area with winter temperatures below 20°F, a cold-climate heat pump is a worthwhile investment.
Dual-Fuel Systems: Heat Pump + Furnace
A dual-fuel system pairs a heat pump with a gas or propane furnace. The heat pump handles heating in moderate weather (above 35–40°F), and the furnace takes over in cold weather. The system automatically switches fuel sources based on outdoor temperature and energy costs. Benefits: the heat pump provides efficient cooling in summer, the furnace provides fast, reliable heat in winter, and the system optimizes between the two for lowest operating cost. Installation requires both outdoor heat pump and indoor furnace with a control that manages the changeover. Dual-fuel systems cost more than either a heat pump or furnace alone but offer the lowest overall operating cost and best comfort across all climates. Many utility companies offer rebates for dual-fuel installations.
Frequently Asked Questions
Frost accumulation on the outdoor coil is normal during heating mode in cold, humid weather. The heat pump periodically runs a defrost cycle (reverse cycle or electric strip heat) to melt the frost. Defrost cycles last 5–15 minutes. Excessive ice buildup suggests a defrost control problem.
During defrost, the outdoor fan stops, the compressor continues running, and steam may rise from the outdoor unit. The indoor auxiliary heat turns on to prevent cold air from blowing into the house. Defrost cycles every 30–90 minutes in cold weather.
No. Heat pumps operate year-round and covering the outdoor unit restricts airflow and can trap moisture. Only cover the unit if the season is ending (summer shutdown for heating-only systems). Never cover a running unit. Trim vegetation away but do not block the unit.
Standard heat pumps lose efficiency below 25–30°F. Cold-climate heat pumps (designed for northern climates) operate efficiently down to -10°F or lower. Check your unit's rated low-temperature operating point. When the heat pump cannot keep up, auxiliary (electric) heat kicks in.
Heat pumps are 2–3x more efficient than electric resistance heat and competitive with natural gas in moderate climates. In very cold climates, the auxiliary electric heat can be expensive. A dual-fuel system (heat pump + gas furnace) provides the best of both: heat pump in moderate weather, gas furnace in extreme cold.
Stay Informed
Get the latest home safety guides and updates delivered to your inbox.